My chiller isn't cooling the water

Problem:

If the water is circulating and coming out of the outlet hose attached to the chiller, and you set the temperature but the water still isn't cooling after a few hours (and the fans are not turning on) The issue is most likely just the settings on the chiller that might have been mixed up.

Please follow the instructions below step by step to fix this issue.

Solution:

To set your chillers target temp you click f for 1 second and adjust using up or down buttons

The temperature settings explained (using the f settings)

To access the function settings you HOLD S for 3 seconds and toggle up or down and to edit a function setting you click S.

F0: Cooling or heating, please choose cooling

F1:3 degree.

Temperature difference.When the chiller hits the target tempt, it will idle between your range. For example, The target temp is 10, when the chiller cool to 10 Degree it will idle and when the water goes up to 13 it will work again.

F2: 40 degree.

Warning of high temperature. If the temperature in the chiller is higher than this, the chiller will not work.

F3: 0 degree.

Warning of low temperature if water temperature lower than this it will not work.

F4: Temperature compensation. The factory default is zero. 

It only needs to be adjusted when the actual water temperature in the tub  is inconsistent with the current water temperature displayed on the screen. Eg if the temperature on the screen is showing 5 but the actual water temperature is 3 then F4 should be set to -2c

F5: 3.

Delay protection set 3. It means after your start the chiller, it will work after 3 mins, it can protect the chiller from big Amperage damage. 

F6: C or F(Celsius or Fahrenheit) You choose C